- Meets standards defined by IEC (International electrotechnical Commission)
- Meets JIS (Japanese Industrial Standard)
- Meets the standards defined by Electrical Appliance and Material Safety Law (PSE)
Molded Case Circuit Breakers (ABS-32FB-15A)
Fuseless, Panelboard Mounting
Over 10,000 units have been selected by valued customers. Space-saving compliant, no-fuse breakers for panelboards.
● DIN rail mounting is possible.
● The panelboard type is compact, allowing it to be used as a distribution panel.
● The lineup now includes 3A ~ 100A rated current.
● JIS Agreement dimensions are 96 mm height and 60 mm depth.
● Accessory equipment can be easily mounted.
● This CE Marking compliant product has passed certification testing.
● Select from breaking capacity of 5 kA and 10 kA.
● Can also be used with 400V power supply systems.
Product Specifications
Specifications
Type | Ampere Frame | Number of Phases | Rated Breaking Current (220 V) |
Rated Current | Model |
Panelboard Type (for distribution panel) |
30 AF | Single-phase | 5kA | 3A | ABS-32FB-3A |
5A | ABS-32FB-5A | ||||
10A | ABS-32FB-10A | ||||
15A | ABS-32FB-15A | ||||
20A | ABS-32FB-20A | ||||
30A | ABS-32FB-30A | ||||
50 AF | 5kA | 40A | ABS-52FB-40A | ||
50A | ABS-52FB-50A | ||||
100 AF | 10kA | 60A | ABS-102FB-60A | ||
75A | ABS-102FB-75A | ||||
100A | ABS-102FB-100A | ||||
30 AF | Three-phase | 5kA | 3A | ABS-33FB-3A | |
5A | ABS-33FB-5A | ||||
10A | ABS-33FB-10A | ||||
15A | ABS-33FB-15A | ||||
20A | ABS-33FB-20A | ||||
30A | ABS-33FB-30A | ||||
50 AF | 5kA | 40A | ABS-53FB-40A | ||
50A | ABS-53FB-50A | ||||
100 AF | 10kA | 60A | ABS-103FB-60A | ||
75A | ABS-103FB-75A | ||||
100A | ABS-103FB-100A |
More Information
Specifications
Ampere Frame | 30AF | 50AF | 100AF | ||||
Type | Panelboard Type | ||||||
Model | ABS-32FB | ABS-33FB | ABS-52FB | ABS-53FB | ABS-102FB | ABS-103FB | |
Rating | Pole Number | 2 | 3 | 2 | 3 | 2 | 3 |
Rated Current (A) | 3, 5, 10, 15, 20, 30 | 40,50 | 60,75,100 | ||||
Rated Voltage AC (V) | 460 | 460 | 460 | ||||
Rated Voltage DC (V) | - | - | - | ||||
Rated Insulation Voltage (V) | 500 | 500 | 500 | ||||
Peak Voltage (V) | 2500 | 2500 | 2500 | ||||
Rated Impulse Voltage KV | 6 | 6 | 6 | ||||
Rated Breaking Capacity (KA) KSC8321 IEC60947-2 |
460 VAC | 2.5 | 2.5 | 5 | |||
380 VAC | 2.5 | 2.5 | 5 | ||||
220 VAC | 5 | 5 | 10 | ||||
100/110 VAC | 5 | 5 | 10 | ||||
Outline Drawing (mm) |
a | 50 | 75 | 50 | 75 | 75 | |
b | 96 | 96 | 96 | ||||
c | 60 | 60 | 60 | ||||
d | 80 | 80 | 80 | ||||
Product Weight (kg) | 0.31 | 0.41 | 0.31 | 0.41 | 0.43 | 0.6 | |
Overcurrent Tripping System | Full Electromagnetic Type | Full Electromagnetic Type | Full Electromagnetic Type | ||||
Installation Configuration | Screw and DIN Rail Mounting *1 | Screw and DIN Rail Mounting *1 | Screw and DIN Rail Mounting *1 | ||||
Terminal Block Screw Size | M5 | M5 | M8 | ||||
Tightening Torque | 2.2 ~ 2.7 N·m | 2.2 ~ 2.7 N·m | 5.4 ~ 7.3 N·m | ||||
Auxiliary Equipment | Auxiliary Contact AX | Mountable | Mountable | Mountable | |||
Alarm Contact AL | |||||||
External Operating Handle D (Surface Mounting) | Non-Mountable | Non-Mountable | Non-Mountable | ||||
External Operating Handle E (Extending) | |||||||
Terminal Cover | Mountable | Mountable | Mountable | ||||
Standard Acquired | Electrical Appliance and Material Safety Act | Acquired | Acquired | Acquired | |||
IEC60947-2 | Acquired | Acquired | Acquired | ||||
CE Marking | Acquired | Acquired | Acquired |
*1: 2 mounting screws are included as standard.
● Inspection after Shutdown
When a breaker shutdown occurs due to accident current, the fuse may be reused or may need to be replaced depending on the situation.
Magnitude of breaking current | Degree of breaker damage | Measures |
Operation within time delay tripping (Overcurrent within approx. 10 times the rated current) |
No abnormality other than exhaust port | Can break overcurrent of 6 times the rated current for up to 50 times (100 A or lower) |
Relatively low current value Shorting Current Large shorting current close to rated breaking capacity |
Carbonization around exhaust port can be observed Carbonization around handle Carbonization around exhaust port Fused metal deposit inside breaker |
Can be Reused Replace with New Parts |
∙ Perform insulation withstand voltage test if insulation resistance value does not reach 5 MΩ.
∙ Can be used temporarily if the standard Peak voltage is achieved, but an early replacement is recommended.
∙ Can be used if both insulation resistance and Peak voltage are sufficient, but check temperature increase does not occur for a certain period of time.
∙ Perform an operation test of the leakage breaker using the test button.
Part Numbers
Loading...
Drawing
Drawing
-
Ampere Frame
- 30AF
- 50 AF
- 100 AF
-
Block Capacity Rating 200V AC(kA)
-
Number of Electrodes
- 2
- 3
-
Current Rating(A)
-
Width(mm)
-
CAD
- 2D
-
Days to Ship
- All
- Same Day
- 4 Days or Less
Specify Alterations
Products like this...
Additional Products in this Category
- Molded Case Circuit Breakers - Fuseless, BH Mini Series, for Branch Circuits
- Molded Case Circuit Breakers - WS Series, PSE/CE/UL/TUV/CCC Compliant
- Molded Case Circuit Breakers - SMU/HRU Series, UL 489 Compliant
- Molded Case Circuit Breakers - G-TWIN AAM Series, Motor Protector
- Molded Case Circuit Breakers - G-TWIN SAM Series, Motor Protector
- Molded Case Circuit Breakers - ELB Series, Compact
- Molded Case Circuit Breakers - Fuseless, NF-C, Economy Value
- Molded Case Circuit Breakers - WS-V Series Control Panel
Your comments help us improve our website. Give feedback