// CODE SNIPPET
R602.7.3 Wood Structural Panel Box Headers
Go To Full Code Chapter
MAXIMUM SPANS FOR WOOD STRUCTURAL PANEL BOX HEADERSa
Wood structural panel box headers shall be constructed in accordance with Figure R602.7.3 and Table R602.7.3.
HEADER CONSTRUCTIONb | HEADER DEPTH (inches) | HOUSE DEPTH (feet) | ||||
24 | 26 | 28 | 30 | 32 | ||
Wood structural panel—one side | 9 | 4 | 4 | 3 | 3 | — |
15
|
5
|
5
|
4
|
3
|
3
|
|
Wood structural panel—both sides | 9 | 7 | 5 | 5 | 4 | 3 |
15
|
8
|
8
|
7
|
7
|
6
|
Related Code Sections
R610.8.1 Wall Construction, Wood Structural Panel Box Headers
Wood structural panel box headers shall be allowed where SIP headers are not applicable. Wood structural panel box headers shall be constructed ...
R602.7.3 Wall Construction, Wood Structural Panel Box Headers
Wood structural panel box headers shall be constructed in accordance with Figure R602.7.3 and Table R602.7.3.
TABLE R602.7.3
MAXIMUM SPANS FOR ...
R602.7 Wall Construction, Headers
Wood structural panel box headers shall be constructed in accordance ...
Section R610 Wall Construction, Structural Insulated Panel Wall Construction
).
Wood structural panel box headers shall ...
R610.8 Wall Construction, Headers
).
Wood structural panel box headers shall be allowed where SIP headers ...